Transformer Oil DGA Calculator: Duval Triangle, IEC 60599 Ratios, Rogers Ratios and TDCG Condition

Writer: Tech Inc
Tech Inc
1 day ago
2 min read

Dissolved gas analysis gives seven numbers; interpreting them takes three or four methods, each with its own thresholds. This calculator applies the standard ones side by side so the diagnosis is not left to a single ratio.

How it works

  • Duval Triangle 1: the percentages of CH₄, C₂H₄ and C₂H₂ among the three place the point in one of seven zones, PD, D1, D2, DT, T1, T2 or T3, using the published zone limits.

  • IEC 60599 basic ratios: C₂H₂/C₂H₄, CH₄/H₂ and C₂H₄/C₂H₆ against the ratio table for each fault class.

  • Rogers ratios: the same three ratios against the six cases of IEEE C57.104-2008 Table 5.

  • TDCG: H₂ + CH₄ + C₂H₆ + C₂H₄ + C₂H₂ + CO against the four-condition table, and each gas against its own limits; the overall condition is the worst.

  • CO₂/CO as a pointer to paper involvement.

Worked example

H₂ 150, CH₄ 200, C₂H₆ 60, C₂H₄ 80, C₂H₂ 3, CO 400, CO₂ 3,500 ppm: Duval places the point in T2 (thermal fault 300 to 700 °C), IEC ratios agree with T2, Rogers gives case 4 (thermal below 700 °C), CO₂/CO 8.75 is in the normal band, and TDCG 893 ppm is Condition 2, above normal: sample more often and watch the trend.

Limits

Fault-type methods are meaningful only when gassing is above normal; a healthy transformer's small numbers will still fall in a zone. The 2019 edition of IEEE C57.104 replaced the fixed Condition table with percentile limits that depend on age and transformer type; the 2008 table here remains a common screening tool. Rates of change matter as much as levels. A reliable diagnosis starts with a representative sample: our transformer oil DGA sampling kit draws syringe and cylinder samples to ASTM D923 without air contact. All Tech Inc. calculators and converters.

Write to mail@techincresearch.com or call +1 (289) 622-1032.

Disclaimer: this calculator and article give estimates from simplified, published equations and the values you enter, for general information only and without warranty. They are not engineering, design, safety or regulatory advice and are no substitute for measurement, the equipment or chemical maker's instructions, the applicable standards or the judgement of a qualified engineer. Do not rely on them for safety-critical decisions. Tech Inc. accepts no liability for loss, damage or injury arising from their use. Equipment specifications are typical and may change; results depend on the fluids and conditions, how the equipment is used and operation in line with the operation manual. See our product information disclaimer and terms of use.