Sample Cooler Duty Calculator: Heat Load, Cooling Water Flow and Approach Temperature

Sample coolers for steam and water analysis (SWAS) and for hot process streams are sized on three numbers: the heat to remove, the cooling water available and the approach temperature. This calculator gives all three.
How it works
Duty Q = m × [cp × (T_in − T_out) + latent heat], latent heat only when the sample arrives as steam.
Cooling water flow = Q ÷ (4.18 × water temperature rise).
LMTD for counter-flow, and area = Q ÷ (U × LMTD) with the overall coefficient you enter; coil-in-shell sample coolers typically reach 1,000 to 1,500 W/m²·K on clean water.
Worked example
1 L/min of condensate at 180 °C cooled to 25 °C with 20 °C cooling water rising to 30 °C: 10.8 kW, 930 kg/h of cooling water, LMTD 42.6 °C and about 0.21 m² at U = 1,200 W/m²·K. The approach is 5 °C, which is practical; a 1 °C approach would need a secondary chiller.
Limits
Cooling water quality sets the fouling and the real U; seawater or tower water needs duplex or titanium coils. ASME PTC 19.11 recommends 25 ± 1 °C at the analyser, which is why a sample chiller follows the primary cooler in most SWAS panels. Our sample coolers and pressure reduction units, tube-in-tube cooler sampling panels, SWAS cation columns, coolers and spares and super duplex seawater coolers are built to these duties. All Tech Inc. calculators and converters.
Related tools: Sample line lag time, Tubing pressure drop, Pressure units (gauge/absolute), Liquid flow units. All 57 calculators and converters.
Write to mail@techincresearch.com or call +1 (289) 622-1032.
Disclaimer: this calculator and article give estimates from simplified, published equations and the values you enter, for general information only and without warranty. They are not engineering, design, safety or regulatory advice and are no substitute for measurement, the equipment or chemical maker's instructions, the applicable standards or the judgement of a qualified engineer. Do not rely on them for safety-critical decisions. Tech Inc. accepts no liability for loss, damage or injury arising from their use. Equipment specifications are typical and may change; results depend on the fluids and conditions, how the equipment is used and operation in line with the operation manual. See our product information disclaimer and terms of use.
Sources
ASME, PTC 19.11 Steam and Water Sampling, Conditioning, and Analysis in the Power Cycle.
Engineering ToolBox, Log Mean Temperature Difference.





Comments