A restriction orifice is the simplest flow limiter there is: a plate with a hole. Sizing it is not hard, but gas flow through it changes character once it chokes, and this calculator handles both regimes.

How it works

  • Liquid: ṁ = Cd E A √(2 ΔP ρ), with the velocity-of-approach factor E = 1 ÷ √(1 − β⁴).

  • Gas, subcritical: isentropic expansion from P₁ to P₂ with the ratio of specific heats k.

  • Gas, choked: once P₂/P₁ falls below the critical ratio, ṁ = Cd A P₁ √(k M ÷ RT) (2/(k+1))^((k+1)/(2(k−1))), independent of P₂.

  • In bore mode the calculator solves for the diameter that passes the required flow; in flow mode it reports the flow through the bore you have.

Worked example

50 Nm³/h of nitrogen from 10 bar(g) to 2 bar(g) at 25 °C through a sharp-edged plate (Cd 0.61) in a 15.8 mm pipe: the flow is choked (P₂/P₁ = 0.27), the bore is 3.78 mm, β = 0.24, and the downstream velocity is 26 m/s.

Limits

Cd depends on plate thickness, edge sharpness and β; 0.61 is for a thin sharp-edged plate with β below 0.75. Large pressure ratios produce high velocity and noise and call for a multi-stage plate. Flashing liquids and two-phase flow are outside the method. Our analyser purge and calibration gas panels, sample conditioning systems and pressure reducing and metering stations use restriction orifices for purge, bypass and flow limiting; the gas flow unit converter handles the reference conditions. All Tech Inc. calculators and converters.

Write to mail@techincresearch.com or call +1 (289) 622-1032.

Disclaimer: this calculator and article give estimates from simplified, published equations and the values you enter, for general information only and without warranty. They are not engineering, design, safety or regulatory advice and are no substitute for measurement, the equipment or chemical maker's instructions, the applicable standards or the judgement of a qualified engineer. Do not rely on them for safety-critical decisions. Tech Inc. accepts no liability for loss, damage or injury arising from their use. Equipment specifications are typical and may change; results depend on the fluids and conditions, how the equipment is used and operation in line with the operation manual. See our product information disclaimer and terms of use.