IEC 60534 Explained: Control Valve Terminology, Sizing Equations, Cavitation and Noise

Control valves are sized, characterised, tested and noise-rated under one family of standards: the IEC 60534 series, Industrial-process control valves, published in the United States as the ANSI/ISA-75 series.
The parts that matter in specification
Part 1, Control valve terminology and general considerations.
Part 2-1, Flow capacity: sizing equations for fluid flow under installed conditions (2011): the equations for incompressible and compressible flow, the flow coefficients C_v and K_v, the liquid pressure recovery factor F_L, the pressure differential ratio factor x_T, the expansion factor Y, the piping geometry factor F_P for reducers, the Reynolds number factor F_R for viscous or small-valve flow, and the choked-flow limits. Part 2-3 gives the test procedures that determine these coefficients.
Part 2-4, Inherent flow characteristics and rangeability: linear, equal-percentage and quick-opening characteristics and how rangeability is defined.
Part 4, Inspection and routine testing; Part 5, Marking.
Part 8-3, Noise considerations: control valve aerodynamic noise prediction method, and Part 8-4 for hydrodynamic noise, which predict the sound pressure level from the valve style, pressure ratio and pipe.
Part 6, Mounting details for positioners; Part 7, Control valve data sheet.
What it means for sizing
Required C_v is calculated from flow, pressures and fluid properties by the Part 2-1 equations; the valve is then chosen so that the duty falls between about 20% and 80% of its rated C_v, the characteristic suits the loop, the cavitation index (σ) or the x_T margin is acceptable, and the predicted noise is below the plant limit (usually 85 dBA). The valve maker's sizing program implements the standard with its own tested coefficients; a hand or online calculation is the check.
Our equipment
Pressure control and letdown valves on our pressure reducing and metering stations, fuel gas conditioning skids and sample conditioning systems are sized this way; the control valve Cv and Kv calculator performs the Part 2-1 basic equations. All our standards guides.
Send your application, materials and the standards your contract names to mail@techincresearch.com or call +1 (289) 622-1032, and we will return a configuration, datasheet and quotation.
This article is our commentary on the standard's published scope, not a substitute for the standard itself; always work to the current edition named in your contract. Equipment specifications may change; performance depends on the application, how the equipment is used and operation in line with the operation manual.
Sources
IEC, IEC 60534-2-1:2011 Industrial-process control valves, Part 2-1: Flow capacity, sizing equations for fluid flow under installed conditions, standard page.
ISA, ANSI/ISA-75 series: control valve standards, ISA standards catalogue.