ISO 8573-1 and ANSI/ISA-7.0.01 Explained: Compressed and Instrument Air Quality Classes

Instrument air feeds control valves, analysers, pneumatic SDI testers and purge systems, and a wet or oily supply quietly ruins all of them. Two standards define what clean means: ISO 8573-1 for compressed air in general and ANSI/ISA-7.0.01 for instrument air specifically.
ISO 8573-1: purity classes
ISO 8573-1:2010 specifies purity classes for three contaminants: solid particles (by count in size bands), water (by pressure dew point, or by liquid content for wet classes) and total oil (aerosol, liquid and vapour). A specification is written as three class numbers, for example ISO 8573-1:2010 [1:2:1], one each for particles, water and oil, with class 0 reserved for user-specified requirements stricter than class 1. The rest of the ISO 8573 series gives the test methods for each contaminant.
ANSI/ISA-7.0.01: instrument air
The ISA standard, published 1996 and still current, sets the quality for air used in pneumatic instruments and controls: a pressure dew point at least 10 °C below the lowest ambient temperature the air system will see (and never above 4 °C at line pressure), a particle size limit of 40 µm, an oil content as close to zero as practical and under 1 ppm w/w, and no corrosive or hazardous contaminants.
What this means at the point of use
A refrigerated dryer gives a dew point around 3 °C; outdoor instrumentation in a cold or desert-night climate needs a desiccant dryer to reach −40 °C.
Filtration: a coalescing filter for oil and water aerosol, then a particulate filter; an activated-carbon stage for oil vapour where analysers or breathing-air are fed.
Point-of-use regulators and filters at analysers, SDI instruments and pneumatic samplers, because the header is rarely as clean as the dryer outlet.
Our equipment
Compressor packages with air dryers, analyser purge and calibration gas panels and the SDI analysers that run on instrument air are specified against these classes; the dew point converter translates the dew point into ppm. All our standards guides.
Send your application, materials and the standards your contract names to mail@techincresearch.com or call +1 (289) 622-1032, and we will return a configuration, datasheet and quotation.
This article is our commentary on the standard's published scope, not a substitute for the standard itself; always work to the current edition named in your contract. Equipment specifications may change; performance depends on the application, how the equipment is used and operation in line with the operation manual.
Sources
ISO, ISO 8573-1:2010 Compressed air, Part 1: Contaminants and purity classes, standard summary page.
ISA, ANSI/ISA-7.0.01-1996 Quality Standard for Instrument Air, standard page.





Comments