API RP 14C Explained: Safety Analysis, SAFE Charts and Surface Safety Systems for Production Facilities

Writer: Tech Inc
Tech Inc
12 minutes ago
2 min read

API Recommended Practice 14C, Analysis, Design, Installation, and Testing of Safety Systems for Offshore Production Facilities (8th edition, 2017) is the document that turns a process flow diagram into a protective system. Its method is also published as ISO 10418, and it is incorporated by reference in US offshore regulations.

What it covers

The practice describes a safety analysis for each process component (wellhead, flowline, separator, heater, compressor, pump, pipeline and so on): the undesirable events (overpressure, underpressure, overflow, leak, excess temperature), the primary and secondary protection against each, and the standard devices that provide it, high and low pressure sensors (PSH, PSL), level sensors (LSH, LSL), temperature sensors (TSH, TSE fusible plugs), shutdown valves (SDV), surface safety valves (SSV), pressure relief (PSV) and flow safety valves. The analysis is documented in Safety Analysis Checklists (SAC) and the Safety Analysis Function Evaluation (SAFE) chart, which maps every sensor to the shutdown function it initiates. It also covers emergency support systems (ESD, fire and gas detection, containment, ventilation), installation, and the testing and documentation of the safety devices through their life.

The design points

  • Two levels of protection for every undesirable event, by different devices.

  • ESD hierarchy: process shutdown of a component, platform or facility shutdown, and emergency shutdown with blowdown, each with defined inputs and effects.

  • Fail-safe actuation: loss of control pressure or power closes the SSV and SDVs.

  • Testing: sensors and valves tested at the intervals the practice sets, with records.

What it means for a wellhead control panel

The panel is where the SAFE chart becomes hardware: pressure pilots sensing flowline pressure, an ESD input, a fusible-plug loop, logic (pneumatic, hydraulic or PLC) that bleeds the actuator supply on any trip, a time delay for start-up, and manual reset. Where a SIL is assigned, IEC 61511 applies on top.

Our equipment

Send your application, materials and the standards your contract names to mail@techincresearch.com or call +1 (289) 622-1032, and we will return a configuration, datasheet and quotation.

This article is our commentary on the standard's published scope, not a substitute for the standard itself; always work to the current edition named in your contract. Equipment specifications may change; performance depends on the application, how the equipment is used and operation in line with the operation manual.