Process Note: How a HIPPS Protects a Pipeline from Overpressure

At a glance. A high-integrity pressure protection system (HIPPS) is a safety instrumented system that shuts off the source of high pressure before it can exceed the design pressure of the equipment downstream. Instead of relieving excess gas to a flare, it stops the flow at its source. This lets operators avoid flaring, protect lower-rated pipelines and plants, and connect high-pressure wells to existing systems. Pipelines, gas plants and offshore platforms across the world use HIPPS, designed to the functional safety standards IEC 61508 and IEC 61511.
How it works
Sensing. Usually three pressure transmitters measure the line pressure independently.
Voting. A safety logic solver trips when two out of three transmitters (2oo3) see high pressure, which avoids both missed trips and spurious ones.
Final elements. Usually two fast-acting shutdown valves in series close the line.
Buffer volume. The piping between the valves and the weak point must absorb the pressure that builds up while the valves close.
Reset. Restart is manual, after the cause has been found.
Design points
Safety integrity level (SIL), set by hazard and risk analysis such as layers of protection analysis. HIPPS are often designed for SIL 3.
Process safety time: the sensing, logic and valve closing time together must be shorter than the time the pressure takes to reach the limit.
Architecture and diagnostics, including separate impulse lines and independent tapping points.
Valve tightness and actuator design, often with partial stroke testing in service.
Proof test interval, which must support the SIL claimed.
Bypass and override management, with clear procedures and records.
A safety requirements specification that documents all of the above.
Common problems
Spurious trips that shut down production without a real overpressure.
Closing too slowly because the actuator or valve was not sized for the process safety time.
Common-cause failures, such as blocked or frozen impulse lines affecting all transmitters.
Proof tests that are late or incomplete.
Bypasses left in place after maintenance.
Where Tech Inc. equipment fits
Tech Inc. supplies the HIPPS high-integrity pressure protection system, PLC- and RTU-based wellhead control systems, hydro-pneumatic and electro-hydraulic wellhead control panels, and the safety valve and valve test bench for maintaining relief valves.
Related reading
This note is general guidance. HIPPS design follows IEC 61511, the project's hazard and risk analysis and the operator's standards.