Membrane filtration removes particles and microbes only while the membrane is intact. A broken hollow fibre, a damaged glue line or a failed O-ring opens a bypass. ASTM D6908 is the standard practice for integrity testing of water filtration membrane systems. The current edition is D6908-25.

What it covers

ASTM's published scope covers determining the integrity of water filtration membrane elements and systems, to verify their ability to reject particles and microbes. It applies to membranes with nominal pore sizes below about 1 µm, in hollow-fibre and flat-sheet (including spiral-wound) configurations, and names the RO, NF and UF classes. The methods are:

  • air-based pressure decay and vacuum hold tests;

  • a soluble dye test;

  • continuous particulate light-scatter monitoring;

  • TOC monitoring (dye and TOC tests generally limited to NF and RO).

Results can track relative change in integrity or, with the standard's equations, estimate integrity as a log reduction value (LRV); for critical applications those estimates should be confirmed experimentally.

Our commentary: direct and indirect tests

  • Direct tests (pressure decay, vacuum hold) check the membrane itself, are sensitive, and are run periodically with the system off line.

  • Indirect tests (particle monitoring, TOC) run continuously during production but are less sensitive.

Plants use both: indirect monitoring to catch sudden failures, direct tests to confirm and quantify.

Where integrity testing starts: the factory

The cheapest place to find a broken fibre or a leaking element is before it ships. Module and element makers test every unit, and research groups test lab modules before trusting their data.