Application Note: Sizing Hydrogen Storage for Fuel-Cell Backup at Telecom Sites and Data Centres

At a glance. A fuel cell can carry a telecom tower or a critical room through a long grid outage, quietly and without exhaust at the site, provided enough hydrogen is stored and ready. Sizing the store starts from the load and the backup time, and ends with a number of cylinders or bundles and a supply skid that changes over by itself.
A worked estimate
Energy needed. A 5 kW load for 8 hours needs 40 kWh.
Hydrogen per kWh. A PEM fuel-cell system typically uses roughly 0.6 to 0.8 Nm³ of hydrogen for each kWh it delivers; take 0.7 Nm³ for this example. 40 kWh × 0.7 ≈ 28 Nm³.
Gas per cylinder. A 50 L cylinder at 200 bar holds roughly 9 Nm³ of hydrogen, of which a little stays behind at the minimum inlet pressure.
Cylinders. 28 Nm³ ÷ about 8.5 Nm³ usable ≈ 3.3, so four cylinders in the duty bank, and the same again in reserve if the site must survive a second outage before the refill arrives.
Use the fuel-cell maker's own consumption figure, the real cylinder contents and the site's refill lead time for the final design.
What the supply skid adds
Duty and reserve banks with automatic changeover, so supply never stops while a bank is replaced.
Filtration and two-stage regulation to the fuel cell's inlet pressure.
Excess-flow valves, relief to a vent stack, hydrogen detection and ventilation.
Remote stock monitoring, so the operator books a refill while the reserve is still full.
Siting
The skid or enclosure stands outdoors or in a ventilated enclosure, with safe distances to building openings, ignition sources and property lines set by the local code, and a vent stack that discharges upwards to a safe location.
Where Tech Inc. equipment fits
Tech Inc. builds the hydrogen supply skid for fuel-cell backup power, hydrogen pressure reducing stations, PEM hydrogen generators and hydrogen fuel quality sampling kits.
Related reading
Sources
Fuel Cells for Backup Power in Telecommunications Facilities (fact sheet) – US Department of Energy
Basic hydrogen properties – Hydrogen Tools, Pacific Northwest National Laboratory
NFPA 2, Hydrogen Technologies Code – National Fire Protection Association
This note is general information. Figures are approximate; every installation is designed to the fuel-cell maker's data and the local codes.