top of page

LPG Vaporisers and Autogas Skids Explained: Steady Vapour, Safe Transfer and Dispensing

Writer: Tech Inc
Tech Inc
2 minutes ago
4 min read
Tech Inc. LPG Vaporiser and Autogas Skid

Bottom line: when a site draws more LPG vapour than its storage tank can boil off on its own, it needs a vaporiser. The vaporiser takes liquid LPG from the tank, heats it electrically or in a water bath, and delivers vapour at a regulated pressure, whatever the weather or the tank level. The same skid family covers transfer pumps for tanker unloading and compact autogas units for filling vehicles. For a firm proposal, send the peak vapour demand, the pressure the consumer needs, the utilities on site and the electrical supply.


What an LPG vaporiser skid is

LPG is stored as a liquid under its own vapour pressure. When a burner draws vapour from the top of the tank, liquid boils to replace it, and the heat for that boiling comes through the tank wall from the surrounding air. At low demand this natural boil-off is enough. At higher demand, or in cold weather, the liquid cools, the tank pressure falls and the supply cannot keep up.


A vaporiser removes that limit by drawing liquid from the tank and supplying the heat itself. The Tech Inc. LPG Vaporiser and Autogas Skid converts liquid LPG to vapour for burners and engines, and transfers or dispenses LPG. Industrial users run furnaces, kilns, dryers and process heaters on vaporised LPG, gas-fired plants use it to fuel burners and engines, filling stations dispense autogas to vehicles, and terminals and depots use transfer skids for tanker unloading and tank-to-tank transfer.


How it works

Liquid LPG flows from the storage tank into the vaporiser, where it is heated until it is fully vapour. The vapour then passes through pressure regulation, which brings it down to the pressure the burner or engine needs, and on to the consumer. Metering on the liquid or vapour side records what has been used, and level and pressure instruments show the operator what the system is doing.


Two kinds of protection sit on the skid. Relief valves vent safely if pressure rises above the design limit. Excess-flow valves close if the flow rises well above normal, as it would if a downstream line were broken. On Tech Inc. skids these are fitted and tested before dispatch.


The main components on the product page are:


  • Vaporiser: electric or water-bath

  • Pressure regulation

  • Relief and excess-flow valves

  • Liquid and vapour metering

  • Level and pressure instrumentation


Transfer and autogas dispensing

Not every LPG duty involves vaporising. A transfer pump skid carries the pump, valves and metering for unloading road tankers and moving product between tanks. A compact autogas filling skid is a packaged unit for dispensing LPG to vehicles. In both cases the metering is there for stock control and billing, so the operator knows exactly what has been received or sold.


Design choices

Heat source. An electric vaporiser is compact and needs only a power supply, with no hot water or steam. A water-bath vaporiser heats the LPG indirectly, through a coil in a heated water bath, which gives a steady vapour output. The choice usually follows the utilities the site already has.


Capacity. Indicative models are TI-LPV-50, TI-LPV-150, TI-LPV-300 and TI-LPV-600, covering about 50 to 600 kg/h of vaporising capacity. Sizes between and beyond these are built to order. Size to the peak demand of all consumers that can run at the same time, not to the daily average, or the outlet pressure will sag when everything fires together.


Single or duty and standby. The model code offers one vaporiser or two in duty and standby. A standby unit lets one vaporiser be serviced while the other keeps the plant running, which matters where a gas interruption stops production.


Codes and electrical supply. Pressure parts are designed to the project's pressure-vessel and piping codes, or to client specification, and the installation must also meet the LPG code that applies at the site, such as NFPA 58 in the United States. The skid is built for the destination supply: 230 V 50 Hz or 110–120 V 60 Hz single-phase, or three-phase to the site supply.


A typical model code reads TI-LPV-150-E-2: an LPG vaporiser skid of about 150 kg/h, electric heating, with two vaporisers in duty and standby.


What to specify

A short, complete enquiry gets a faster and more accurate proposal. Include:


  • The duty: vaporising, transfer, autogas dispensing, or a combination

  • Peak and minimum vapour demand in kg/h, and the burners or engines it serves

  • The outlet vapour pressure each consumer needs

  • The LPG grade stored (propane, butane or a mixture)

  • Preferred heat source and the utilities available on site

  • One vaporiser, or duty and standby

  • Transfer or dispensing flow rates, where those duties apply

  • The pressure-vessel, piping and LPG installation codes that apply

  • Electrical supply, hazardous-area classification and the lowest ambient temperature on site


Each skid is engineered to your P&ID, data sheets and company standards, with drawings submitted for approval before manufacture and factory acceptance testing with client or third-party inspection. Model data, design data and ordering codes are on the LPG Vaporiser and Autogas Skid product page. To start a selection, send the model code or your process data through the enquiry page, and we will confirm it with a datasheet and GA drawing before manufacture.


Comments