top of page

CNG Decompression Skids Explained: Letting Down Trailer Gas Without Freezing

Writer: Tech Inc
Tech Inc
2 minutes ago
3 min read
Tech Inc. CNG Decompression Skid

Bottom line: a CNG decompression skid lets compressed natural gas delivered by road down from storage or trailer pressure to the pressure a user's burners and engines need. The pressure drop is large, and gas cools sharply as it expands, so heating is part of the design, not an extra. Filtration, heating, staged regulation, over-pressure protection and metering sit on one fixed or mobile unit. Get the peak flow, the inlet and outlet pressures and the available heating utility right, and the rest of the design follows.


What a CNG decompression skid is

Many factories and sites sit beyond the reach of the gas grid. A virtual pipeline closes that gap: gas is compressed at a mother station, carried by trailer and let down at the customer's site. The decompression skid is the last link in that chain. The Tech Inc. CNG Decompression Skid reduces compressed natural gas from storage or trailer pressure to user pressure, with heating to prevent freezing, so industrial users and temporary sites can run on natural gas where there is no pipeline.


Mobile units have a second role. They provide temporary gas supply during pipeline maintenance or commissioning, or until a permanent connection is built, and then move on to the next site.


How it works

Gas leaves the trailer at high pressure and passes first through inlet filtration, which protects the regulators and valves from dirt carried over from the trailer and hoses.


It is then heated. When gas expands through a regulator its temperature falls, and across a drop from trailer pressure to a few bar the fall is large enough to ice up regulators, freeze moisture and chill downstream piping below its design temperature. The heater adds enough energy before the pressure is reduced to offset that cooling, so the gas reaches the user at a usable temperature.


Pressure is then reduced in stages. Two- or three-stage regulation shares the drop between regulators, which keeps each one in a comfortable operating range and gives a stable outlet pressure as the trailer empties and its pressure falls. Slam-shut valves close and relief valves vent if pressure downstream rises too high, guarding the user's system. Metering records the gas delivered for billing, and odorisation can be added where the gas feeds a distribution network.


The main components on the product page are:


  • Inlet filtration

  • Heater: water bath, hot-water exchanger or electric

  • Two- or three-stage regulators

  • Slam-shut and relief valves

  • Metering

  • Optional odorisation


Design choices

Pressures. Tech Inc. designs take inlet pressures up to 250 bar (3,630 psi)(g) and give outlet pressures typically between 0.1 and 10 bar (1 to 145 psi)(g), or to client specification. Materials are selected for the inlet pressure and design conditions.


Heating method. A water bath, a hot-water exchanger or an electric heater can supply the heat, sized to offset the cooling from the pressure drop. A hot-water exchanger suits sites that already have a hot-water or boiler system; electric heating suits sites where power is easier to supply than hot water.


Number of stages. A single stage can handle a smaller pressure drop. For the full drop from trailer pressure to user pressure, multiple stages share the load and give steadier control.


Fixed or mobile. A fixed skid is a permanent installation fed from trailer bays or on-site storage. A trailer or container unit is self-contained and moves between sites as demand changes.


Capacity. Indicative models are TI-CDS-100, TI-CDS-500, TI-CDS-1500 and TI-CDS-3000, for gas flows of about 100 to 3,000 Sm³/h. Sizes between and beyond these are built to order. A typical code, TI-CDS-500-W-2, describes a skid of about 500 Sm³/h with water-bath heating and two reduction stages.


Electrical supply. The skid is built for the destination: 230 V 50 Hz or 110–120 V 60 Hz single-phase, or three-phase to the site supply.


What to specify

For a selection we can stand behind, include:


  • Peak, normal and minimum gas demand in Sm³/h, and how it varies over the day

  • Trailer or storage pressure at the start and at the end of discharge

  • Required outlet pressure, and any intermediate pressure needed by other consumers

  • Gas composition, and whether the gas is odorised already or needs odorisation

  • Heating utility available: hot water, power, or neither

  • Fixed skid, trailer or container

  • Metering requirement for billing

  • Design codes and company standards that apply

  • Electrical supply, hazardous-area classification and the ambient temperature range on site


Each skid is engineered to your P&ID, data sheets and company standards, with drawings submitted for approval and factory acceptance testing with client or third-party inspection. Full design data and the ordering code are on the CNG Decompression Skid product page. Send the model code or your process data through the enquiry page, and we will confirm the selection with a datasheet and GA drawing before manufacture.


Comments


bottom of page