Fuel Gas Conditioning Skids: How to Size Filtration, Superheat and Pressure Control
At a glance. A fuel gas conditioning skid removes liquids and solids, heats the gas so it stays well above its hydrocarbon dew point after pressure letdown, and regulates it to the pressure the consumer needs. Ask for coalescing filtration to about 0.3 µm, superheat of typically 28 °C (50 °F) above the hydrocarbon dew point at the consumer, and heating sized for the coldest gas and the largest pressure drop.
Why does fuel gas need conditioning?
Liquid droplets in fuel gas cause flame instability, hot spots and damage to combustion hardware, and solids erode fuel nozzles and control valves. Gas that is only just above its dew point can condense when its pressure is reduced, so a turbine that looks well protected at the pipeline can still receive liquid at the burner. Most turbine makers therefore specify a filtration level and a minimum superheat above the hydrocarbon dew point in their fuel gas specifications.
What goes on the skid?
Stage | Purpose |
Inlet knock-out or scrubber | Removes slugs and bulk liquid |
Filter separator or coalescer | Removes fine aerosols and solids, typically to 0.3 µm |
Heater | Raises the gas temperature to give the required superheat |
Pressure regulation | Reduces pressure to the consumer's supply pressure, with slam-shut and relief protection |
Final filter (optional) | Protects the fuel system downstream of the heater |
Metering (optional) | Measures fuel consumption or custody flow |
Duplex filters, or a spare filter separator, let elements be changed without stopping the consumer.
Why must heating come before letdown?
Natural gas cools as its pressure drops, through the Joule–Thomson effect, by roughly half a degree Celsius for every bar of pressure reduction, depending on composition. A letdown of 40 bar can therefore cool the gas by around 20 °C. The heater must add enough heat to cover that cooling and still leave the required superheat at the consumer, at the coldest inlet temperature and the highest flow.
Electric or shell-and-tube heating?
Electric heaters are compact, simple to control and suit smaller flows or sites with spare power. Shell-and-tube or water-bath heaters using hot water, steam or another heat source suit larger flows where waste heat is available. The choice usually follows the site's utilities and the heat duty.
Specification checklist
Gas composition, including heavy hydrocarbons and water
Inlet pressure and temperature range
Flow at minimum, normal and maximum demand
Consumer's fuel gas specification: pressure, filtration and superheat
Heater type and available utilities
Design code: ASME VIII vessels and ASME B31.3 piping
Hazardous-area zone and ambient range
Instrumentation, metering and control interface
Tech Inc. fuel gas conditioning
Tech Inc. builds fuel gas conditioning skids, filter separator and coalescer skids, pressure reducing and metering stations and gas metering skids, and supplies replacement gas coalescer elements. Send your gas data and the consumer's fuel specification to mail@techincresearch.com.
Frequently asked questions
How much superheat does a gas turbine need?
Turbine makers commonly ask for about 28 °C (50 °F) above the hydrocarbon dew point at the turbine inlet. Always follow the turbine's own fuel gas specification.
What filtration level is usual?
Coalescing filtration removing liquids and solids down to about 0.3 µm is typical for turbine fuel gas.
Why not simply heat the gas downstream of the regulator?
The cooling happens across the regulator itself, so liquid can form there and in the pipework before a downstream heater. Heating upstream keeps the gas dry through the letdown.
Can one skid feed several turbines?
Yes, if it is sized for their combined demand and the pressure control suits their load changes. Spare filtration keeps all units running during element changes.